Overview
The LW36-126 outdoor high-voltage AC sulfur hexafluoride circuit breaker adopts a three-phase porcelain column single-break mechanism. The three phases are equipped with a spring operating mechanism, arranged in the center, and the three phases are linked, so the appearance is novel and exquisite. The circuit breaker uses SF6 gas as the insulation and arc extinguishing medium. During operation, the three poles of the circuit breaker are connected with SF6 gas, and a pointer density relay is used to monitor its pressure and density.
Structural features
1. The circuit breaker adopts a three-phase porcelain column single-break structure. The three phases are equipped with a spring operating mechanism. They are arranged in the center and the three phases are linked, so the appearance is novel and exquisite. The circuit breaker uses SF6 gas as the insulation and arc extinguishing medium. During operation, the three poles of the circuit breaker are connected with SF6 gas, and a pointer density relay is used to monitor its pressure and density. Due to the adoption of the self-energy arc extinguishing principle and the optimized design in the circuit breaker motion system, the mechanical efficiency is effectively improved and the operating power is minimized;
2. Excellent breaking performance and long electrical life;
3. The installation base frame and support are made of integrally bent steel plates, and the surface treatment is all hot-dip galvanized. The exposed fasteners are made of high-strength materials and hot-dip galvanized, or stainless steel standard parts, and the mechanism box shell is made of stainless steel. , so the product has excellent corrosion resistance;
4. The machine has high reliability and can be operated frequently;
5. Due to the inherently high dielectric strength of sulfur hexafluoride gas and the circuit breaker using optimal contact movement, the circuit breaker breaks capacitive current without reignition;
6. The external insulation level is high, the external insulation is designed with a large creepage distance, the specific creepage distance is ≥31mm/kV, and it has excellent pollution resistance. Can operate safely in harsh environments;
7. Strong current carrying capacity: The temperature rise test is conducted at 1.2 times the rated current of 3150A, that is, 3780A, and there is still a large margin for temperature rise at each point;
8. The overall appearance and structure of the product are compact, easy to install and debug on site, and require little maintenance work.
Main technical parameters of circuit breaker
|
Project |
Unit |
Value |
|
|
Rated voltage |
KV |
126 |
|
|
Rated frequency |
Hz |
50 |
|
|
Rated current |
A |
3150 |
|
|
Rated short circuit breaking current |
KA |
40 |
|
|
Rated short-time withstand current |
KA |
40 |
|
|
Rated peak withstand current |
KA |
100 |
|
|
Rated short circuit duration |
S |
3 |
|
|
Rated short circuit making current (peak value) |
KA |
100 |
|
|
Near zone fault interrupting current |
KA |
36/30 |
|
|
Rated line charging breaking current |
A |
31.5 |
|
|
Rated out-of-step breaking current |
KA |
10 |
|
|
Cumulative breaking times under rated short-circuit breaking current |
times |
20 |
|
|
first opening factor |
1.5 |
||
|
SF6 gas pressure (20℃) |
MPa |
0.5 |
|
|
Rated voltage of control loop and auxiliary loop power supply |
DC220V DC110V |
||
|
Rated operating sequence |
O-0.3S-CO-180S-CO |
||
|
Rated main circuit resistance |
μΩ |
≤55 |
|
|
Circuit breaker mechanical durability |
times |
10000 |
|
|
Static pulling force of terminal block |
Horizontal and portrait FshA |
N |
1250 |
|
Horizontal transverse FshB |
N |
750 |
|
|
Vertical direction FtVm |
N |
1000 |
|
|
SF6 gas annual leakage rate |
% |
≤1 |
|
|
SF6 gas moisture content (V/V) |
ppm |
≤150±4 |
|
|
Contact stroke |
mm |
150±4 |
|
|
contact stroke |
mm |
25 |
|
Insulation level
|
Project |
Value |
|
|
1min power frequency withstand voltage (effective value, dry type, wet type) |
KV between fractures |
230 |
|
KV between poles or pole to ground |
230 |
|
|
Lightning impulse withstand voltage (peak) (full wave 1.2/50μS) |
KV between fractures |
550 |
|
KV between poles or pole to ground |
550 |
|
|
5min power frequency withstand voltage (effective value) when SF6 gas has zero gauge pressure |
KV between fractures |
95 |
|
Pole to ground KV |
95 |
|
Mechanical properties
|
Project |
Unit |
Value |
|
Upper and lower limits of opening time |
ms |
27±3 |
|
Upper and lower limits of closing time |
ms |
100 20 |
|
opening and closing time |
ms |
≤300 |
|
closing and opening time |
ms |
≤50 |
|
Opening synchronicity |
ms |
≤3 |
|
Closing synchronicity |
ms |
≤5 |
|
Breaking time |
ms |
60 |
|
Opening speed (10ms after opening) |
m/s |
3.9 |
|
Closing speed (5ms before closing) |
m/s |
2.8±0.3 |
Appearance and installation diagram

Hot Tags: lw36-126 outdoor high voltage ac sulfur hexafluoride circuit breaker, China lw36-126 outdoor high voltage ac sulfur hexafluoride circuit breaker manufacturers, suppliers, factory, sf6 circuit breaker for sustainability requirements, sf6 circuit breaker for emission reduction requirements, sf6 circuit breaker for value added projects, low voltage sf6 circuit breaker, sf6 circuit breaker for innovation requirements, medium voltage sf6 circuit breaker