Products
LW16-40.5 Outdoor Sulfur Hexafluoride Circuit Breaker

LW16-40.5 Outdoor Sulfur Hexafluoride Circuit Breaker

Overview LW16-40.5 outdoor sulfur hexafluoride circuit breaker is an outdoor device used in AC 50Hz three-phase power systems. It is used for control and protection in industrial and mining enterprises, power plants and sidebands. This product can be operated frequently and can be used as a...

Overview

    LW16-40.5 outdoor sulfur hexafluoride circuit breaker is an outdoor device used in AC 50Hz three-phase power systems. It is used for control and protection in industrial and mining enterprises, power plants and sidebands. This product can be operated frequently and can be used as a contact circuit breaker and a circuit breaker for capacitor banks and reactor banks. The built-in current transformer can be used for measurement and protection. It can directly replace the SW2-35 oil-less circuit breaker. Equipped with a transition bracket, it can replace various types of oil-rich circuit breakers. It is an ideal oil-free circuit breaker in the 35KV power system. device.

    LW16-40.5 circuit breaker is equipped with CT14-A AC and DC dual-purpose spring operating mechanism.

Technical Parameters

Project

Unit

Value

Rated voltage

KV

40.5

Rated insulation level

1min power frequency withstand voltage

KV

95

Lightning impulse withstand voltage

KV

185

Rated frequency

Hz

50

Rated current

A

1600,2000

Rated short circuit breaking current

KA

25 (reclosing), 31.5 (single point)

Rated short circuit making current (peak value)

KA

63

Rated short-time withstand current

KA

25

Rated short circuit duration

S

4

Rated peak withstand current

KA

63

Rated operating sequence

 

O-0.3S-CO-180S-CO

Rated breaking current of a single capacitor bank

A

400

Rated out-of-step breaking current

KA

6.3

Rated out-of-phase breaking current

KA

21.75

Mechanical life test

times

3000

Rated current cumulative breaking times

times

2000

Rated short circuit breaking current (25KA) cumulative breaking times

times

21

Gate opening time

At rated or maximum operating voltage

S

≤0.06

at minimum operating voltage

S

≤0.1

Closing time

S

≤0.15

Rated pressure of SF6 gas (gauge pressure 20℃)

MPa

0.6±0.015

SF6 gas supply alarm pressure (gauge pressure 20℃)

MPa

0.55±0.015

Minimum functional pressure of SF6 gas (gauge pressure 20℃)

MPa

0.52±0.015

SF6 gas annual leakage rate

%/year

≤1

SF6 gas trace moisture content

V/V

≤150×10-6

CT14-A mechanism opening and closing coil rated voltage

AC

V

220

DC

110,220

CT14-A mechanism energy storage motor rated voltage

AC

V

220,380

DC

110,220

SF6 gas weight

Kg

Normal: 2.5, with CT: 6, with extra height, CT: 8

Circuit breaker weight

Kg

1000

Short circuit external insulation leakage ratio distance

mm/KV

≥31

Porcelain sleeve leakage distance

mm

≥1255

Conductive rod row spacing

mm

65±2

Minimum air insulation distance

mm

440

Three-level opening synchronicity

ms

≤2

Main circuit resistance

μΩ

Normal≤40 with CT≤60

Rigid speed (at rated voltage)

m/s

2.4±0.2

Just closing speed (at rated voltage)

m/s

≥2

Appearance and installation diagram

product-936-746

Hot Tags: lw16-40.5 outdoor sulfur hexafluoride circuit breaker, China lw16-40.5 outdoor sulfur hexafluoride circuit breaker manufacturers, suppliers, factory, indoor sf6 circuit breaker, sf6 circuit breaker for emission reduction requirements, medium voltage sf6 circuit breaker, sf6 circuit breaker for market competitiveness requirements, sf6 circuit breaker for inspection and testing, sf6 circuit breaker for energy conservation requirements

Send Inquiry