Structural features
1. The circuit breaker adopts the principle of rotating arc extinguishing, which uses the magnetic field force exerted by the arc current to cause the arc to rotate at high speed along a certain section. Since the mass of the arc is relatively light, during high-speed rotation, the arc is gradually lengthened and continuously exposed to fresh air. SF6 gas is extinguished when cooled. This structure circuit breaker has the advantages of strong arc extinguishing ability, long electrical life, no current blocking phenomenon when breaking small currents, and no operating overvoltage. At the same time, it requires low operating power and has high reliability.
2. The circuit breaker adopts a miniaturized spring operating mechanism, which has the advantages of reliable action, long mechanical life, and simple control. The spring operating mechanism can store energy manually or electrically, close and open manually or electrically, and has a reclosing function.
3. The circuit breaker box material is welded from 304 stainless steel with a thickness of 3mm. It has a fully airtight structure and a protection level of not less than IP67. There are easy-to-observe and obvious opening and closing position indicators and energy storage status indicators on the box. The indicator is reliably connected to the operating mechanism, and the indicating action is reliable. The box has a carrying handle to avoid pulling out the cable casing.
Main electrical parameters
|
Name |
Unit |
Value |
|
|
Rated voltage |
KV |
12 |
|
|
Rated frequency |
Hz |
50 |
|
|
Rated current |
A |
630 |
|
|
Rated short circuit breaking current |
KA |
20 |
|
|
Rated short circuit duration |
S |
4 |
|
|
Rated short-time withstand current |
KA |
20 |
|
|
Rated peak withstand current |
KA |
50 |
|
|
Rated cable charging current |
A |
25 |
|
|
Rated operating sequence |
Minutes-0.3S-Total points-180S-Total points |
||
|
Rated working pressure (when gauge pressure is 20°C) |
MPa |
0.35 |
|
|
Minimum functional pressure (when gauge pressure is 20°C) |
MPa |
0.25 |
|
|
1min power frequency withstand voltage (under the lowest working pressure) |
alternately and relatively |
KV |
42 |
|
fracture |
KV |
48 |
|
|
Rated lightning impulse withstand voltage (at the lowest working pressure) |
alternately and relatively |
KV |
75 |
|
fracture |
KV |
85 |
|
|
Rated mechanical stability times |
times |
10000 |
|
|
SF6 gas annual leakage rate |
≤0.05% |
||
|
Rated operating voltage |
V |
DC24 |
|
Main mechanical properties parameters
|
Name |
Unit |
Value |
|
Contact spacing |
mm |
36~38 |
|
Contact overtravel |
mm |
20±2 |
|
Closing time |
ms |
40~80 |
|
Opening time |
ms |
30~60 |
|
Closing and opening at different stages |
ms |
≤2 |
|
Just closing speed |
m/s |
2.6±0.2 |
|
Just divided speed |
m/s |
3.2±0.3 |
|
Main circuit resistance |
μΩ |
≤120 |
Built-in three-phase current transformer parameters
|
Project |
Unit |
Value |
|
|
Rated current ratio |
600/1 |
600/S |
|
|
Accuracy level |
Times |
0.5/5P10 |
|
|
Polarity |
minus polarity |
||
|
Rated load |
VA |
1 |
2.5 |
Built-in zero sequence current transformer parameters
|
Project |
Unit |
Value |
|
Rated current ratio |
20/1 |
|
|
Accuracy level |
pole |
When the primary side input current is 1A to the rated current, the relative error is ≤3%. When the primary current input is 100A, the relative error of the protection is ≤10%. |
|
Polarity |
minus polarity |
|
|
Rated load |
VA |
0.5VA |
Shape and installation dimensions

Hot Tags: lw3-12 primary and secondary fusion sulfur hexafluoride circuit breaker, China lw3-12 primary and secondary fusion sulfur hexafluoride circuit breaker manufacturers, suppliers, factory, sf6 circuit breaker for inventory management, sf6 circuit breaker for inspection and testing, sf6 circuit breaker for cost minimization requirements, sf6 circuit breaker for compliance, low voltage sf6 circuit breaker, sf6 circuit breaker for market competitiveness requirements