Products
LN2-40.5 Outdoor High Voltage Sulfur Hexafluoride Circuit Breaker

LN2-40.5 Outdoor High Voltage Sulfur Hexafluoride Circuit Breaker

Overview LN2-40.5 indoor high-voltage sulfur hexafluoride circuit breaker is an indoor device in an AC 50HZ three-phase system. It can be used for protection and control in industrial and mining enterprises, power plants and substations. And can be used in frequent operating locations. It can...

Overview

    LN2-40.5 indoor high-voltage sulfur hexafluoride circuit breaker is an indoor device in an AC 50HZ three-phase system. It can be used for protection and control in industrial and mining enterprises, power plants and substations. And can be used in frequent operating locations. It can also be used as a tie circuit breaker and a switching capacitor grouper.

    LN2-40.5 type is equipped with CT10-A spring operating mechanism and can also be equipped with CD10IIIG electromagnetic operating mechanism.

Use environmental conditions

The ambient temperature shall not be higher than +40℃ and not lower than -10℃.

The altitude does not exceed 3000m.

Relative temperature is not greater than 90% (20℃)

There is no risk of fire, explosion, serious pollution, chemical corrosion or severe vibration.

Technical Parameters

Project

Unit

LN2-40.5/1250A-25

Rated voltage

KV

40.5

Maximum working voltage

KV

40.5

Rated insulation level

Lightning impulse withstand voltage (full wave)

KV

185

Power frequency withstand voltage (1min)

KV

95

Rated frequency

HZ

50

Rated current

A

1250

Rated short circuit breaking current

KA

25

Rated operating sequence

 

Minutes-0.3S-Total points-180S-Total points

Rated short circuit making current

KA

63

Rated dynamic stable current

(peak value)

63

Rated thermal stable current

KA

25

Rated thermal stabilization time

S

4

Switching a single capacitor bank to break current

A

400

Rated out-of-step breaking current

KA

6.3

Cumulative breaking times at rated current

times

2000

Number of interruptions under rated short-circuit breaking current

times

16

Mechanical life

Equipped with CT10-A spring mechanism

times

6000

Equipped with CD10IIIG electromagnetic mechanism

times

5000

Closing time

spring mechanism

S

≤0.15

Electromagnetic mechanism

S

≤0.2

inherent opening time

When the operating voltage is

lowest

S

≤0.1

Rated to the highest

S

≤0.07

Rated pressure of sulfur hexafluoride gas (gauge pressure at 20°C)

MPa

0.65

Sulfur hexafluoride gas alarm pressure (gauge pressure at 20°C)

MPa

0.42

Sulfur hexafluoride gas locking pressure (gauge pressure at 20°C)

MPa

0.40

Annual air leakage rate

 

≤1%

Moisture content of sulfur hexafluoride gas

PPM(V)

150

Rated operating voltage with CT10-A spring operating mechanism

Closing coil

V

DC 48.110.220

opening coil

V

DC 48.110.220

electric motor

V

DC 110.220

Rated operating voltage equipped with CD10IIIG electromagnetic actuator

Closing coil

V

DC 110.220

opening coil

V

DC 48.110.220

weight

Circuit breaker body

Kg

135

Sulfur hexafluoride gas

Kg

1.5

product-934-329

Hot Tags: ln2-40.5 outdoor high voltage sulfur hexafluoride circuit breaker, China ln2-40.5 outdoor high voltage sulfur hexafluoride circuit breaker manufacturers, suppliers, factory, sf6 circuit breaker for cost minimization requirements, sf6 circuit breaker for quality control, sf6 gas insulated circuit breaker, sf6 circuit breaker for procurement projects, sf6 circuit breaker for emission reduction requirements, sf6 circuit breaker for investment projects