Overview
LN2-40.5 indoor high-voltage sulfur hexafluoride circuit breaker is an indoor device in an AC 50HZ three-phase system. It can be used for protection and control in industrial and mining enterprises, power plants and substations. And can be used in frequent operating locations. It can also be used as a tie circuit breaker and a switching capacitor grouper.
LN2-40.5 type is equipped with CT10-A spring operating mechanism and can also be equipped with CD10IIIG electromagnetic operating mechanism.
Use environmental conditions
The ambient temperature shall not be higher than +40℃ and not lower than -10℃.
The altitude does not exceed 3000m.
Relative temperature is not greater than 90% (20℃)
There is no risk of fire, explosion, serious pollution, chemical corrosion or severe vibration.
Technical Parameters
|
Project |
Unit |
LN2-40.5/1250A-25 |
|||
|
Rated voltage |
KV |
40.5 |
|||
|
Maximum working voltage |
KV |
40.5 |
|||
|
Rated insulation level |
Lightning impulse withstand voltage (full wave) |
KV |
185 |
||
|
Power frequency withstand voltage (1min) |
KV |
95 |
|||
|
Rated frequency |
HZ |
50 |
|||
|
Rated current |
A |
1250 |
|||
|
Rated short circuit breaking current |
KA |
25 |
|||
|
Rated operating sequence |
Minutes-0.3S-Total points-180S-Total points |
||||
|
Rated short circuit making current |
KA |
63 |
|||
|
Rated dynamic stable current |
(peak value) |
63 |
|||
|
Rated thermal stable current |
KA |
25 |
|||
|
Rated thermal stabilization time |
S |
4 |
|||
|
Switching a single capacitor bank to break current |
A |
400 |
|||
|
Rated out-of-step breaking current |
KA |
6.3 |
|||
|
Cumulative breaking times at rated current |
times |
2000 |
|||
|
Number of interruptions under rated short-circuit breaking current |
times |
16 |
|||
|
Mechanical life |
Equipped with CT10-A spring mechanism |
times |
6000 |
||
|
Equipped with CD10IIIG electromagnetic mechanism |
times |
5000 |
|||
|
Closing time |
spring mechanism |
S |
≤0.15 |
||
|
Electromagnetic mechanism |
S |
≤0.2 |
|||
|
inherent opening time |
When the operating voltage is |
lowest |
S |
≤0.1 |
|
|
Rated to the highest |
S |
≤0.07 |
|||
|
Rated pressure of sulfur hexafluoride gas (gauge pressure at 20°C) |
MPa |
0.65 |
|||
|
Sulfur hexafluoride gas alarm pressure (gauge pressure at 20°C) |
MPa |
0.42 |
|||
|
Sulfur hexafluoride gas locking pressure (gauge pressure at 20°C) |
MPa |
0.40 |
|||
|
Annual air leakage rate |
≤1% |
||||
|
Moisture content of sulfur hexafluoride gas |
PPM(V) |
150 |
|||
|
Rated operating voltage with CT10-A spring operating mechanism |
Closing coil |
V |
DC 48.110.220 |
||
|
opening coil |
V |
DC 48.110.220 |
|||
|
electric motor |
V |
DC 110.220 |
|||
|
Rated operating voltage equipped with CD10IIIG electromagnetic actuator |
Closing coil |
V |
DC 110.220 |
||
|
opening coil |
V |
DC 48.110.220 |
|||
|
weight |
Circuit breaker body |
Kg |
135 |
||
|
Sulfur hexafluoride gas |
Kg |
1.5 |
|||

Hot Tags: ln2-40.5 outdoor high voltage sulfur hexafluoride circuit breaker, China ln2-40.5 outdoor high voltage sulfur hexafluoride circuit breaker manufacturers, suppliers, factory, sf6 circuit breaker for cost minimization requirements, sf6 circuit breaker for quality control, sf6 gas insulated circuit breaker, sf6 circuit breaker for procurement projects, sf6 circuit breaker for emission reduction requirements, sf6 circuit breaker for investment projects