Overview
The ZCW10-40.5 type open combined electrical appliance is a complete set of combined electrical appliances that uses air as the external insulation and SF6 gas as the arc extinguishing medium. It is used for the control and protection of three-phase AC 72.5KV power transmission and distribution system, and can also be used for contact circuit breakers and switching capacitor banks. It is suitable for urban substations, enterprise substations, and mountainous substations where land is scarce.
Model meaning

Technical Parameters
|
Project |
Unit |
Value |
|
|
Rated voltage |
KV |
40.5 |
|
|
Rated insulation level |
Lightning impulse withstand voltage (full wave peak) |
KV |
185 |
|
Power frequency withstand voltage (1min) |
KV |
95 |
|
|
Rated current |
A |
2000 |
|
|
Mechanical life |
times |
10000 |
|
|
Rated pressure of sulfur hexafluoride gas (gauge pressure at 20°C) |
MPa |
0.5 |
|
|
Alarm pressure/minimum functional pressure (20℃ gauge pressure) |
MPa |
0.45 |
|
|
Rated short circuit breaking current |
KA |
40 |
|
|
Rated short circuit making current (peak value) |
KA |
100 |
|
|
Rated short-time withstand current (thermal stable current) |
KA |
40 |
|
|
Rated short circuit withstand current (dynamic stable current) |
KA |
100 |
|
|
Rated out-of-step breaking current |
KA |
10 |
|
|
Cumulative breaking times under rated short-circuit breaking current |
times |
12 |
|
|
Cumulative breaking time at rated short-circuit breaking current |
S |
4 |
|
|
Closing time (under rated operating voltage) |
S |
≤0.15 |
|
|
Opening time (under rated operating voltage) |
S |
≤0.06 |
|
|
Rated operating sequence |
|
C-0.3S-CO-180S-CO |
|
|
Rated switching current of a single capacitor bank |
A |
400 |
|
|
Annual air leakage rate |
% |
≤0.4 |
|
|
Moisture content of sulfur hexafluoride gas (V/V) |
|
≤150x10-6 |
|
|
Rated operating voltage with CT14 spring operating mechanism |
|
|
|
|
Closing coil, opening coil voltage |
V |
DC 110 220 |
|
|
Energy storage motor voltage |
V |
AC,DC 110 220 |
|
|
Sulfur hexafluoride gas weight |
Kg |
8 |
|
|
Weight of circuit breaker (including operating mechanism) |
Kg |
1400 |
|

Hot Tags: zcw10-40.5l open combination electrical appliance, China zcw10-40.5l open combination electrical appliance manufacturers, suppliers, factory, sf6 circuit breaker for business growth requirements, sf6 circuit breaker for emission reduction requirements, sf6 circuit breaker for national standards, sf6 circuit breaker for customer satisfaction requirements, sf6 circuit breaker for environmental standards, sf6 circuit breaker for value added projects