When the transformer is in operation or undergoing a high-voltage test, the iron core and its metal parts are in different positions in a strong electric field, and the potentials induced by static electricity are also different. This results in a potential difference between the iron core and the metal parts or the grounding body, and intermittent spark discharges between metal parts with different potentials. This discharge will decompose the transformer oil and damage the solid insulation. In order to avoid the above situation, the iron core and its metal parts (except the through-core screw) must be reliably grounded. Due to the shielding effect of the iron core, the through-core screw has a potential that is similar to that of the iron core, so it does not need to be grounded again. Since the insulation resistance between the silicon steel sheets of the iron core is very small, only one sheet needs to be grounded, and all the laminations of the iron core can be considered to be grounded.
The following points should be noted when grounding:
1) The iron core is only allowed to be grounded at one point, and only single-line connections are allowed between the parts that need to be grounded. If there are more than two grounding points in the iron core, a closed loop may be formed between the grounding points. When a large magnetic field passes through this closed loop, an electromotive force will be induced in the loop and a current will be caused. The magnitude of the current depends on the magnitude of the induced electromotive force and the impedance value of the closed loop. When the current is large, it will cause local overheating failure and even burn the iron core.
2) The grounding plate should have a certain strength and cross-sectional area, and is generally made of 0.3mm×20mm, 0.3mm×30mm or 0.3mm×40mmr tinned copper sheet. The depth of the grounding plate inserted into the iron core is not less than 30mm for distribution transformers, not less than 70mm for main transformers, and up to 140mm for large transformers.
3) The grounding plate should be close to the clamp and should not touch the end face of the iron yoke to prevent the silicon steel sheet of the iron yoke from short-circuiting.
4) Other metal accessories of the body should be grounded.
5) The core contact should generally be set on the low-voltage side.