What We Look For When Specifying Lightning Arresters

Mar 07, 2026 Leave a message

  Our team has spent the last fifteen years working on power projects across Southeast Asia and the Middle East. We have supplied arresters to coastal substations in Vietnam, desert sites in Saudi Arabia, and high lightning areas in Indonesia. Along the way, we have seen which specifications actually matter once the equipment is installed and left to run.

  Take rated voltage. At a 220kV substation in eastern Indonesia, the utility was replacing arresters every two years. The system voltage regularly hit 240kV during light load periods. The original 192kV arresters failed during temporary overvoltages from line switching. Replacement with 216kV units solved the problem. For 132kV systems where voltage reaches 145kV, we now specify 144kV class. For 66kV, 84kV class. For 33kV distribution, 42kV class. The rule is simple: 1.2 to 1.25 times maximum operating voltage.

  Energy rating is another factor that gets overlooked. Western Java sees over 100 thunderstorm days per year. Lines there take multiple strikes in a single storm. Arresters rated 3kJ per kV were failing within three years. Moving to 5kJ per kV minimum reduced failures significantly. For lines longer than 20km or areas with high lightning density, we specify 8 to 10kJ per kV on transformer protection. The cost difference is small compared to sending a crew to a remote tower.

  Creepage distance and housing material determine how long an arrester lasts in harsh environments. At that same Indonesian site, the original porcelain arresters had adequate creepage numbers on paper. But salt fog coated everything during wet season. Porcelain wets out completely and contamination builds up. The silicone rubber units installed later stay dry during fog-water beads and runs off. In the UAE, we have seen sand absorb overnight moisture and become conductive on porcelain. Same fix applies: silicone rubber with creepage 31mm per kV or higher. For inland low-pollution sites, 25mm per kV may work but we rarely go below that for critical assets.

  Disconnectors are inexpensive protection. Before we added them on that Indonesian line, a failed arrester caused a permanent line fault. Crews had to patrol the whole line to find it. With disconnectors, the failed unit drops out and the line stays energized. Replacement happens on schedule. Essential for remote lines, optional for substations.

  Residual voltage needs to coordinate with transformer insulation. A 132kV transformer in Malaysia failed during a storm several years ago. The arresters were correctly rated for voltage but residual at 10kA was 580kV. Transformer BIL was 650kV-only 12 percent margin. Replacement with arresters rated at 520kV residual solved it. We now check for at least 20 percent margin below equipment BIL. For 66kV transformers with BIL 325kV, residual at 5kA should be under 260kV. For 220kV with BIL 950kV, residual at 10kA under 760kV.

  Pressure relief prevents explosive failure. We witnessed an arrester explode because the pressure relief rating was below available fault current. It damaged adjacent switchgear. We now verify pressure relief matches site fault level-typically 40kA for one second at transmission level.

For coastal and desert projects, here is what our engineers typically specify: rated voltage at least 1.2 times maximum system voltage, energy rating 5kJ per kV minimum (8 to 10kJ for high lightning areas), creepage 31mm per kV minimum with silicone rubber housing, disconnector on line arresters, residual voltage with 20 percent margin below BIL, pressure relief matching fault current, and compliance with IEC 60099-4 with independent lab type tests.

  These are the parameters we have learned to check after years of site work. If your team is working on a project in a coastal or desert environment and wants to review the numbers, we are glad to help.