1. Vacuum circuit breaker anti-jumping:
It plays a protective role and requires relay control. When the closing signal is not removed, the closing circuit is disconnected after the closing action, ensuring that under certain conditions, the circuit breaker will be closed immediately after the system controls the circuit breaker to open.
2. The function of vacuum circuit breaker blocking:
1. The circuit breaker cannot be closed before the lock is unlocked;
2. After the circuit breaker is closed, the closing circuit is cut off, so that the circuit breaker cannot be closed again even if the auxiliary switch action in the circuit breaker status is unreliable.
3. "Latching" is a measure to prevent electrical misoperation. What we electrical operators are most afraid of is misoperation, including:
(1) Pull and close the isolating switch with load;
(2) Close the switch with a grounding wire (grounding knife);
(3) Personnel mistakenly enters the live space;
(4) Mis-opening or mis-closing of circuit breaker;
(5). Hang the grounding wire when it is live (close the grounding knife).
3. The locking of the vacuum circuit breaker includes:
Mechanical locking is a locking method in which the mechanical structures of the switchgear operating mechanism restrict each other to achieve mutual interlocking.
Electromagnetic locking uses the auxiliary contacts of circuit breakers, isolating switches, circuit breaker cabinet doors, etc. to connect or disconnect the electromagnetic lock power supply of isolating switches, switch cabinet doors, etc. that need to be locked, so that the operating mechanism cannot operate, thereby realizing the switching equipment. interlocking. This kind of locking device has a simple principle and is easy to implement. Locking can be achieved between non-identical switching devices; it is relatively reliable to operate in a dry environment. However, limited by our "national conditions", most of them are installed on indoor equipment of 35 kV and below. During use, due to various reasons, the auxiliary transfer switch cannot switch normally, and the electromagnetic lock cannot meet the sealing requirements and is corroded by moisture, causing the lock to often fail. To prevent accidental locking of outdoor high-voltage switchgear, electrical logic locking is mostly used.