The three main reasons for transformer temperature rise are that the transformer temperature rise is too high during operation, mainly due to poor contact of the tap changer, short circuit between winding turns or solid, and insulation damage between core silicon steel plates, which leads to excessive and rapid temperature rise of the transformer.
According to the operation management regulations, the top oil temperature of the natural circulation cooling oil-immersed transformer should generally not exceed 85℃.
Apply for load reduction immediately when the top oil temperature reaches 95℃. The alarm temperature of the top oil temperature of the transformer is 800℃, the cooling fan starts at 65℃, and returns to 55℃ (unless otherwise specified by the manufacturer).
The transformer temperature rise is too high, which can be defined according to the following two situations: exceeding the maximum allowable value of the top oil temperature of the transformer; at the same ambient temperature. Under the same load, the top oil temperature is 10℃ higher than the standard value.
Reasons for excessive transformer temperature rise:
1. Poor contact of the tap changer
Due to the increase in contact resistance, contact heating occurs, which will increase power loss and increase oil temperature at the least, and burn the tap changer at the worst.
By measuring the resistance of the high-voltage winding, the contact condition of the tap changer can be judged, and it can also be judged by the frequent movement of light gas or oil sample inspection. If the tap changer has poor contact, the hanging core should be repaired.
2. Short circuit between turns or solid layers of the winding
Since the short-circuited part of the winding will generate a large circulating current, the temperature of the winding will rise, causing the temperature of the transformer to rise too high.
By measuring the resistance of the winding, the turn-to-turn or solid short circuit can be judged. If the short-circuit ignition generates an arc, the oil decomposes to produce gas, causing the light gas to move frequently. Turn-to-turn or solid short circuit faults can only be handled by hanging core inspection.
3. Damage to the insulation between the silicon steel plates of the iron core
Damage to the insulation between the silicon steel plates or the insulation tube of the through bolt will cause eddy currents in the iron core, which will lead to excessive temperature rise.
The long-term increase in oil temperature will accelerate the aging of the oil, so it can be roughly judged by oil test analysis. The iron core fault can only be checked and handled by hanging core.