Two measures to prevent drop-out fuse failure

Jul 03, 2024 Leave a message

The drop-out fuse is a short-circuit protection switch commonly used on 10KV distribution lines and distribution transformers. It is economical, easy to operate, and highly adaptable. In actual working conditions, the drop-out fuse may fail due to various reasons. To avoid these problems, the following measures can be taken:

I. Reasonable selection of drop-out fuses and fuse elements

1. Drop-out fuses are suitable for outdoor environments. There should be no conductive dust, corrosive gases, flammable and explosive substances in the air, and the annual temperature difference should be within 40°C. When selecting a drop-out fuse, select a rated current greater than or equal to the rated current of the fuse, and ensure that the three-phase short-circuit capacity of the protected system is less than the upper limit of the opening capacity of the drop-out fuse and greater than the lower limit of the rated opening capacity.
2. When selecting a fuse, ensure that it can be quickly blown when a short circuit occurs inside the distribution transformer or in the high and low voltage outlet bushings. It is also necessary to consider that the fusing characteristics of the fuse should be coordinated with the upper protection time.

||, Correct installation of drop-out fuses
1. During installation, the fuse should be pulled tight to prevent the contacts from heating;
2. The fuse should be installed on the frame stably and firmly without shaking;
3. The fuse tube should be tilted downward at an angle of 15°-30°;
4. The installation height should not be less than 4.5m;
5. The length of the fuse tube should be adjusted appropriately;
6. The phase-to-phase distance should be greater than 60cm.