A leakage circuit breaker is a switch that automatically operates when the leakage current in the circuit exceeds a predetermined value. Commonly used leakage circuit breakers are divided into two types: voltage type and current type, and the current type is further divided into electromagnetic type and electronic type. Voltage type leakage circuit breakers are used in low-voltage power grids where the neutral point of the transformer is not grounded. Its characteristic is that when a person is electrocuted, a relatively high voltage appears between the neutral line and the ground, causing the relay to operate and the power switch to trip. Current type leakage circuit breakers are mainly used in low-voltage distribution systems where the neutral point of the transformer is grounded. Its characteristic is that when a person is electrocuted, a leakage current is detected by the zero-sequence current transformer, causing the relay to operate and the power switch to disconnect.
The following are two faults encountered when using leakage circuit breakers and their solutions:
Fault 1: The leakage circuit breaker trips as soon as it is put into operation
(I) The three-phase power lines, including the neutral line, do not pass through the zero-sequence current transformer in the same direction. Correct the wiring.
(ii) The circuits with and without leakage circuit breakers are electrically connected. Just separate the two circuits.
(iii) There is a live and ground load in the circuit. Just eliminate such loads.
(iv) There is repeated grounding of the working neutral line passing through the zero-sequence current transformer. The repeated grounding should be eliminated.
(v) The leakage circuit breaker itself is faulty and should be replaced.
Fault 2: Misoperation of leakage circuit breaker
(i) Caused by overvoltage. If the circuit breaker can be operated when an operating overvoltage occurs in the circuit, a delayed or impulse voltage non-operating leakage circuit breaker can be selected. A resistor-capacitor absorption circuit can also be installed between the contacts to suppress the overvoltage. An overvoltage absorption device can also be added to the circuit.
(ii) Electromagnetic interference. If there are magnetic devices or high-power electrical equipment nearby, the installation position of the leakage circuit breaker should be adjusted to stay away from such electrical components.
(iii) Circulating current influence. If two transformers are operated in parallel, they both have their own grounding. Since the impedance of the two transformers cannot be equal, a circulating current will be generated in the grounding wire, causing the circuit breaker to operate. You can remove one grounding wire. In addition, the same transformer supplies power to the same load through two parallel circuits. The currents in the two circuits cannot be the same, and circulating currents may also occur. Therefore, the two circuits should be operated separately.
(IV) The insulation resistance of the working neutral line is reduced. When the insulation resistance of the working neutral line is reduced, if the three-phase load is unbalanced, a relatively large working current will appear on the neutral line and flow to other branches through the ground, so that leakage current can appear on each leakage circuit breaker, causing the circuit breaker to malfunction.
(V) Improper grounding. If the neutral line is repeatedly grounded, it will cause the leakage circuit breaker to malfunction.
(VI) The influence of overload or short circuit. If the leakage circuit breaker has short circuit protection and overcurrent protection at the same time, it will malfunction when the setting current of the overcurrent protection release is not appropriate. At this time, you can adjust the setting current value.