The function of high voltage isolating switch

Jul 22, 2024 Leave a message

    The high-voltage isolating switch itself does not have an arc extinguishing function. The high-voltage fuse cannot be used to make or break current, nor can it interrupt short-circuit current. It can only be used for certain switching operations that will not cause strong arcs, such as voltage transformers, High-voltage control appliances for lightning arresters, transformers, metering cabinets and other equipment, or connected to high-voltage circuit breakers to ensure reliability during power outages.

    The high-voltage isolating switch is not allowed to operate with load. The normal operating range of the 10kv isolating switch is the high-voltage wall bushing that connects and disconnects the voltage transformer and lightning rod, the charging circuit of the busbar, and the no-load capacitance flow of no more than 5A. No-load transformers with line and on-off excitation currents not exceeding 2A.

    The switching capacity of the high-voltage isolating switch for no-load lines is limited based on the fact that the opening and closing length of the outdoor high-voltage isolating switch cannot exceed the no-load current of the overhead line of 10km. For high-voltage load switches, for unloaded cable lines, the capacitance current of high-voltage current-limiting fuses is higher than that of overhead circuits of the same length. Therefore, the length cannot be used to limit it. The 5A level can only be used as the standard for high-voltage isolating switches.

    The on-off performance of the high-voltage isolating switch for no-load transformers is stipulated according to the old-fashioned transformers from around the 1950s. However, due to the large no-load current of the transformers at that time, the limit of the isolating switch's on-off capability was also low. Although the current isolating switches and transformers have greatly changed in performance, due to the lack of a clearly defined range, drop-out fuses can only be rated to not exceed 2A.

Send Inquiry