The starting point for selection is understanding the system's grounding method. Power systems are generally classified into two categories: effectively grounded (where the neutral point is directly grounded) and non-effectively grounded (where the neutral is ungrounded or grounded via arc suppression coils or high resistance). These grounding methods determine the extent to which healthy phase voltages rise during a single-phase ground fault. In effectively grounded systems, the voltage increase on non-faulted phases is limited. In non-effectively grounded systems, however, the healthy phase voltage can rise to the line-to-line voltage and remain at this level for a certain period. This distinction forms a critical basis for subsequent calculations.
Several key parameters of the surge arrester are central to the selection process. The continuous operating voltage (Uc) refers to the power-frequency RMS voltage that can be applied across the arrester terminals over the long term. It must be higher than the maximum continuous phase voltage at the installation point. For non-effectively grounded systems, considering the voltage rise on healthy phases during a ground fault, Uc should not be less than the system's maximum line-to-line operating voltage.
An even more important parameter is the rated voltage (Ur), which represents the maximum temporary overvoltage (power frequency) RMS value that the arrester can withstand. This is the most critical parameter in the selection process, as it directly determines whether the arrester can survive abnormal system conditions. If the rated voltage is set too low, the arrester may experience thermal runaway and fail under severe temporary overvoltages. If it is too high, the protective level (residual voltage) may be compromised, reducing its effectiveness in safeguarding equipment insulation.
When determining the rated voltage, the influence of the system grounding method must be fully considered. For effectively grounded systems, the arrester's rated voltage is typically selected at 75% to 80% of the system's maximum operating voltage. For non-effectively grounded systems, where temporary overvoltages are more severe, the rated voltage should be at least 100% of the maximum operating voltage, and in some cases, up to 110% to ensure an adequate safety margin. For example, in a 10kV (with a maximum operating voltage of 12kV) non-effectively grounded system, it is common practice to select an arrester with a rated voltage of 17kV.
After preliminarily determining the continuous operating voltage and rated voltage, insulation coordination verification is essential. This involves checking that the residual voltage of the arrester under the nominal discharge current is lower than the lightning impulse insulation level (BIL) of the protected equipment, such as transformers or switches, with a protective margin of at least 15% to 25%. This step is necessary to ensure that the arrester limits overvoltages to a safe range for the equipment during operation.
Practical selection must also consider the installation environment. In high-altitude areas, reduced air density can diminish the external insulation strength of arresters, potentially necessitating the use of products with a higher rated voltage or specially designed高原-type arresters. Additionally, depending on the installation location-such as power stations, distribution systems, or transmission lines-the appropriate type of arrester (station-class, distribution-class, or line-type) should be selected, as they differ significantly in energy-handling capacity and performance.
In summary, selecting surge arresters based on system voltage is a systematic engineering decision. It requires technicians to have a deep understanding of system operation, accurately interpret various arrester parameters, and perform rigorous calculations and verifications. The goal is to choose an arrester that ensures its own safety while providing reliable protection for other equipment. Relying solely on nominal voltage for selection can introduce significant risks to the safe operation of the power system.