1. When the melt melts, the cause of the melt must be carefully analyzed. Possible reasons are:

(1) Normal fuse due to short circuit fault or overload;

(2) The melt is used for too long, and the melt is mistakenly broken due to oxidation or high temperature during operation;

(3) There is mechanical damage during the installation of the melt, which reduces the cross-sectional area and causes false disconnection during operation.

2. When replacing the melt, it is required to:

(1) Before installing a new melt, find out the reason why the melt has blown. If you are not sure of the cause, do not replace the melt for trial operation;

(2) When replacing a new melt, check whether the rating of the melt matches the equipment being protected;

(3) When replacing the new melt, check the internal burns of the fuse tube. If there are serious burns, the fuse tube should be replaced at the same time. When the porcelain fused pipe is damaged, it is not allowed to replace it with pipes of other materials. When replacing a packing fuse, pay attention to the packing.

3. Maintenance work when the fuse fails is as follows:

(1) Remove dust and check the contact condition of the contact points;

(2) Check the appearance of the fuse (remove the fuse tube) to see if it is damaged and deformed, and whether the porcelain parts have traces of discharge flash;

(3) Check whether the fuses and melts match the circuit or equipment to be protected, and investigate promptly if there are any problems;

(4) Pay attention to check the N wire in the TN grounding system and the ground protection wire of the equipment. The use of fuses is not allowed;

(5) When maintaining and inspecting the fuse, the power supply should be cut off according to safety regulations, and the fuse tube should not be taken out while it is powered on.