Abnormal contact overheating is the most common fault manifestation in isolating switches, rooted in abnormal increases in contact resistance:
Increased Oxidation Corrosion: Copper or aluminum contacts exposed long-term to air form high-resistance oxide layers, acting as insulating barriers between conductors, converting significant electrical energy into heat during operation.
typically ≥80N), tight contact cannot be maintained, drastically reducing effective contact area. Insufficient pressure is often caused by spring fatigue, overheating-induced annealing, or improper installation.
Accumulated Arc Erosion Damage: High-current switching or prolonged overheating burns contact surfaces, creating uneven pits or nodules, further degrading contact quality.
Precision Maintenance Procedures:
evenly apply power-grade composite conductive paste. Its metallic fillers fill microscopic gaps, reducing contact resistance and delaying oxidation.
exceeds 1mm or severe deformation/cracking exists, the entire contact finger assembly must be replaced. After installation, measure and adjust spring pressure to the qualified range (≥80N).
Mechanism issues directly affect the switch's opening/closing function and can even cause severe accidents:
Lubrication Failure: Lubricating grease (especially ordinary grease) in outdoor mechanism boxes hardens easily at low temperatures or degrades/dries out over time, losing lubricity.
must be <0.5mm), generating high mechanical resistance.
Failure-to-Operate (Rejection): Mechanism shows no movement during electrical operation.
Electrical Circuit Faults: Missing motor power supply, broken control circuit wires, faulty limit switches, contactor failures, etc.
Systematic Solutions:
Stiffness Handling:
low-temperature grease (e.g., Molykote 33 MR) to key rotating/sliding parts (bearings, gears, slides) to ensure wide-temperature-range lubrication.
concentricity deviation <0.5mm. Correct bent linkage rods.
Failure-to-Operate Handling:
Strict Interlock Check: Before operation, always confirm the status of all related grounding switches and that interlock devices are correctly released.
Electrical Circuit Troubleshooting: Use a multimeter to sequentially measure motor power supply, control circuit continuity, limit switch signals, contactor coil, and contact status. Strictly prohibit forced manual operation before identifying the cause, as excessive torque easily fractures brittle porcelain columns, causing major accidents.
III. Insulator Maintenance: Defense Against Damage and Pollution Flashover
Insulators perform the critical roles of electrical isolation and mechanical support; their failure has severe consequences.
Maintenance & Emergency Strategies:
Emergency Damage Handling:
This is a non-negotiable safety requirement.
temporary measure, with replacement scheduled ASAP.
Proactive Pollution Flashover Prevention:
Room Temperature Vulcanized Silicone Rubber (RTV) anti-pollution flashover coating. RTV coating possesses excellent hydrophobicity transfer properties, effectively suppressing moisture absorption by contaminants and leakage current development.