Analysis of key technologies for lightning protection system design for wind power and photovoltaic stations and grounding resistance reduction in deserts

Apr 26, 2025 Leave a message

    I. Wind turbine blade lightning protection and box transformer lightning arrester coordinated protection

System coordination principle

The modern wind turbine blade lightning protection system adopts the "lightning terminal-down conductor" system, which forms a low-impedance discharge channel through the combination of the blade tip pre-set lightning terminal and the carbon fiber down conductor. As the core equipment of the unit, the box transformer needs to be equipped with a metal oxide lightning arrester (MOA) to achieve secondary protection. The key to the coordinated work of the two lies in the potential balance control of the discharge path.

Protection distance specification requirements

    Engineering practice shows that when the distance between the grounding point of the lightning induction system and the box transformer MOA exceeds 50 meters, the lightning strike may generate a potential difference of more than 15kV. It is recommended to adopt the "double ring grounding network + multi-point interconnection" architecture to ensure that the distance between the two is ≤50 meters. The measured data of a wind farm in Inner Mongolia shows that the residual pressure at the equipment end is reduced by 42% and the electromagnetic interference intensity is reduced by 58% at a distance of 35 meters.

Typical design errors

(1) Over-reliance on a single lightning protection device and neglect of system-level coordination

(2) Segmented design of grounding grid leads to abnormal potential gradient

(3) Use of ordinary cables instead of dedicated leakage conductors

(4) Failure to consider the impact of dynamic lightning current distribution on MOA selection

II. Optimization of grounding system for desert photovoltaic power stations

Challenges of geological characteristics

    Typical desert soil resistivity can reach more than 5000Ω·m. The power frequency grounding resistance of conventional vertical grounding electrodes (3m deep) is greater than 120Ω, which cannot meet the specification requirement of ≤4Ω for photovoltaic arrays. The dry and hot environment causes the failure rate of traditional chemical resistance reducing agents to reach 70% within 3 months.

Composite resistance reducing technology system

(1) Bentonite grounding module: Use MX-6 sodium-based bentonite module with a size of 600×400×60mm. The effective diffusion area of ​​a single module is 18㎡. When laying in parallel, maintain a spacing of 3 times the module length to form a three-dimensional diffusion network.

(2) Ion slow-release system: PH-9 slow-release agent is configured, containing metal salt ratio: 32% magnesium sulfate + 15% copper sulfate + 23% sodium chloride. It is continuously released at a rate of 3.5g/(cm²·year) through a ceramic slow-release tube to maintain soil ion concentration>0.6mol/L.

Key points of construction control

(1) Adopt "丰"-shaped grid layout, main grid depth ≥1.2m

(2) Backfill 20cm thick clay-wood chip mixed layer (3:1) around the module

(3) Node connection adopts exothermic welding, overlap length ≥100mm

(4) Regularly detect ion concentration, replenishment cycle ≤18 months

III. Comparison of typical cases

After adopting this scheme, a 200MW photovoltaic power station in Gansu:

Initial grounding resistance: 3.8Ω (standard value 4Ω)

Resistance value after 3 years: 4.2Ω (conventional scheme >15Ω in the same period)

Lightning damage rate decreased by 83%

Annual maintenance cost decreased by 65%

    Conclusion:

The new lightning protection system effectively solves the problem of lightning protection and grounding in the special environment of new energy stations through precise electromagnetic coordination design and material technology innovation. In actual projects, it is necessary to dynamically optimize parameters in combination with geological exploration data, establish a full life cycle monitoring system, and ensure the continuous and reliable operation of the protection system.