Products Description
FS series valve-type zinc oxide arresters are used to protect electrical equipment such as distribution transformers and cable heads from atmospheric overvoltage damage.
Details of Product
Applicable to:
1. Indoor and outdoor: The ambient temperature of the place of use is -40℃~+40℃.
2. The altitude of the place of use does not exceed 1000m. In areas higher than 1000m, plateau type arresters are used.
3. The phase-to-ground power frequency voltage that may occur at the installation location should not be greater than the rated voltage of the arrester.
Not suitable for: places with serious pollution and severe vibration
The FS series arrester consists of a spark gap and a valve plate stacked in a single column in a porcelain sleeve, and both ends of the porcelain sleeve are sealed with rubber. Iron clamps and wiring bolts are provided for installation and wiring.
FS8 series arresters are modified products of FS4 series arresters. Their internal structure and electrical characteristics are the same as those of FS4 series.
But it has the following characteristics:
(1) The product is filled with high-purity dry nitrogen to prevent corona from generating ozone, thereby ensuring stable product performance.
(2) The upper metal cover is replaced with a porcelain cover structure, which solves the problem of corrosion of the upper iron cover.
(3) Use special bolts to protrude wiring from the upper end of the porcelain sleeve to replace the terminals on the welder's metal to avoid desoldering of the terminals.
(4) The upper end of the porcelain sleeve is sealed with double layers of rubber to ensure reliable sealing performance.
The porcelain sleeve and iron cover of the plateau arrester are sealed by metal and porcelain welding, which has excellent sealing performance and can be used in areas with any altitude.

Precautions:
1.Preventive tests should be performed on the arrester before and after operation. The arrester in operation should be tested every 1 to 2 years. The items include:
(1)To measure the leakage current, apply the DC voltage specified in the characteristics table to both ends of the arrester (the ripple of the DC voltage shall not be greater than ±1.5%). The leakage current flowing through the arrester shall comply with the provisions of the characteristics table.
(2)Insulation resistance test: Use a 2.5kV megger to measure the insulation resistance. The resistance value is not specified, but the results of each test should be similar.
(3)Power frequency discharge voltage measurement: Apply 50Hz AC voltage to the arrester end, and on the premise that the voltage value can be read correctly, increase the voltage evenly from zero until the arrester discharges. The current flowing through the arrester during discharge should be limited to 0.2~0.7A, and the power supply should be cut off within 0.5s after discharge. The number of measurements for each arrester shall not be less than 3 times, and the time interval for each measurement shall not be less than 10 seconds. Its value shall comply with the provisions in the characteristic table.
2.During transportation and storage, the arrester should be placed upright.
3.During operation, the original painted part of the arrester should be painted every 1-2 years.
4.During installation, the horizontal pulling force of the top lead of the arrester should not be greater than 294N (30kgf).
Hot Tags: valve type lightning arrester, China valve type lightning arrester manufacturers, suppliers, factory, voltage surge arrester, surge protection for geothermal power, overvoltage limiting device, voltage spike arrester for geothermal power, Lightning Arrester for substation, surge protection for biomass power